In the specialized field of pharmaceutical compounding, the Pharmacy Cleanroom AHU is the engine that ensures drug stability and patient safety. Whether for hazardous oncology compounding (Negative Pressure) or sterile IV preparation (Positive Pressure), these units must meet USP 797/800 and ISO 14644 standards.
Under the Energy Efficiency and Conservation Act (EECA) 2024, EKG (Malaysia) SDN BHD engineers these systems to maintain a 5-star Building Energy Intensity (BEI) while overcoming the significant air resistance of clinical filtration.
Pharmacy AHUs are engineered based on the type of pharmaceutical preparation occurring within the cleanroom.
Sterile Non-Hazardous (Positive Pressure): The AHU maintains a pressure of +12.5 Pa to +15 Pa relative to the ante-room. This "piston" of air ensures that no unfiltered contaminants from the hospital corridor enter the compounding zone.
Hazardous Compounding (Negative Pressure): For chemotherapy and oncology, the AHU creates a -12.5 Pa gradient. This ensures that toxic drug vapors or powders are contained within the room and pulled into the exhaust filtration system, protecting the pharmacy staff.
ISO Class 5 / 7 / 8: We design for the "Cascade" effect, where air moves from the cleanest ISO 5 (Compounding Aisle) to the ISO 7 (Buffer Room) and finally the ISO 8 (Ante-room).
To prevent the AHU itself from becoming a contamination risk, we utilize a "Biologically Inert" construction.
Internal Lining (SUS 304/316): The internal skin is medical-grade stainless steel. This withstands the aggressive chemical sanitization and Vaporized Hydrogen Peroxide (VHP) cycles used in clinical pharmacies.
TB2 Thermal Break Casing: This is mandatory in Malaysia's humidity to prevent casing "sweat." Moisture on the unit exterior can lead to mold, which is a critical failure during an MOH (Ministry of Health) clinical audit.
L1-Class Airtightness: At the high static pressures required for HEPA filters, any leakage would destabilize the room pressure. Our L1-rated construction ensures a perfect seal.
The AHU operates as a multi-stage purification barrier:
Stage 1 (G4/F7): Primary filters to capture bulk dust and protect the internal IE5 motors.
Stage 2 (F9/E10): Secondary filters to remove fine particles and bio-aerosols.
Terminal Stage (H14 HEPA): Achieving 99.999% efficiency at 0.3 microns. For hazardous labs, we utilize Bag-In/Bag-Out (BIBO) exhaust housings to safely contain drug residues.
UV-C Germicidal (UVGI): 254nm lamps are integrated to bathe the cooling coils, preventing the growth of "bio-film" and ensuring maximum energy efficiency.
Pharmaceutical cleanrooms require high Air Change Rates (ACR), which can be energy-intensive. EKG optimizes these systems to maintain a low Specific Fan Power (SFP):
IE5 Direct-Drive EC Fan Arrays: These modular fans use 30% less energy than legacy belt-driven fans. They provide N+1 Redundancy, ensuring the cleanroom never loses its pressure regime if a single fan fails.
VAV & Occupancy Tracking: Our systems can ramp down during non-operational hours while still maintaining the minimum pressure required by USP standards, significantly lowering the BEI.
EnMS Integrated Monitoring: All environmental data (Pressure, Temp, Humidity, $kW$) is logged for the Energy Commission's statutory audits.
| Metric | Standard Medical AHU | EKG Pharmacy Cleanroom AHU |
| USP Compliance | N/A | USP 797 & 800 Certified |
| Filtration | F9 / E10 | H14 HEPA (Terminal) |
| Pressure Range | Neutral | Strict $\pm$ 12.5 Pa to 15 Pa |
| Internal Skin | Painted GI | Stainless Steel (SUS 304/316) |
| Humidty Control | General Comfort | Precision ($\pm$ 2% RH) |
| Energy Strategy | Standard | Star-Rated (EECA 2024 Optimized) |
Technical Integrity: We provide the Validation Documentation (IQ/OQ) and Airflow Mapping required for clinical license renewals.
Precision BIM Coordination: We model the complex interaction between the AHU, terminal HEPA units, and pharmacy workstations to ensure a clash-free installation.
BOMBA-Compliant Safety: All internal materials and gaskets are non-shedding and fire-rated (Class 0 or B1).