Product Summary |
|
|
Precision external closed cooling water circulator with the temp. control accuracy±0.1°C. |
|
|
|
|
Features |
|
|
Provide high-precision circulatin water with the temp. range -10°C+80°C and temp. control accuracy±0.1°C. |
|
Powerful cooling capacity. |
|
Continuous monitoring for water level, abnormal refrigerator pressure, refrigerator operation, circulation pump operation, etc.. |
|
Configurated with auto stop, auto start operations, temp. output terminal, deviation correction, external communication (RS485), etc.. |
|
Overcurrent ELB, self-diagnosis, key lock, refrigerator overload protector, refrigerator delay timer of protection, refrigerator pressure detection, float switch preventing pump idling, bypass for protecting circulating pump, auto overheat protection, overheat protector, etc.. |
|
|
|
|
|
|
|
Specifications |
|
|
Specification Item |
Details |
|
Model |
CFA611 |
|
Method |
External closed circulation |
|
Operating temperature range |
-10~+80°C |
|
Temperature control accuracy |
±0.1°C JTM K05 (at 20°C) |
|
Temperature setting, display |
Digital setting and display |
|
Temperature indicating unit |
0.1°C |
|
Cooling capacity |
Approx. 850W (731 Kcal/h), at fluid temp.10°C |
|
Operating environmental temp. range |
5~35°C |
|
Temperature control |
PID control |
|
Temperature sensor |
Temp. controller: Pt thermal resistance, overheat protection: K thermocouple |
|
Refrigerator, refrigerant |
Air cooling 600W, R404A |
|
Circulating pump |
Magnetic drive pump 65W |
|
Unit circulation ability (50/60Hz) Max. flow, Pump capacity |
12.7/14.4L/min (22.0 / 25.0L/min) |
|
Unit circulation ability (50/60Hz) Max. lift, Pump capacity |
10.0/13.4m (10.0 / 13.5m) |
|
Heater |
Stainless steel heater, 2.5KW |
|
Cooling coil |
SUS brazing plate type |
|
External circulation nozzle |
Rc3/8 |
|
Safety device |
Overcurrent ELB, Self-diagnosis, Refrigerator overload protector, Refrigerator delay timer of protection, Refrigerator pressure detection, Float switch preventing pump idling, |
|
Safety device |
Bypass for protecting circulating pump, Auto overheat protection, Overheat protector, etc.. |
|
Other functions |
Drain valve, Condenser filter screen, Deviation correction, External communication (RS485), Refrigerator pressure indicator, Key lock, Temp. output terminal |
|
Accessories |
Drain pipe, Overflow pipe |
|
External dimensions(W×D×H mm) |
380×535×955mm |
|
Remarks(dimensions) |
Bath capacity 6L, Bath dimension W127xD317xH160mm |
|
Power Source |
AC220V 17A Single-phase with step down transformer |
|
Weight |
76kg |