| Technical data | EL1088 |
|---|---|
| Connection technology | 1-wire |
| Specification | ground switching “0”: 18…30 V DC, “1”: 0…7 V DC, typ. 3 mA input current |
| Number of inputs | 8 |
| Nominal voltage | 24 V DC (-15%/+20%) |
| “0” signal voltage | 18…30 V |
| “1” signal voltage | 0…7 V |
| Input current | typ. 3 mA |
| Input filter | typ. 3 ms |
| Distributed clocks | – |
| Current consumption power contacts | typ. 25 mA |
| Current consumption E-bus | typ. 90 mA |
| Electrical isolation | 500 V (E-bus/field potential) |
| Configuration | no address or configuration setting |
| Weight | approx. 50 g |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/see documentation |
| Pluggable wiring level | for all ESxxxx terminals |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx, DNV |
| Ex marking |
ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |