| Feature | Description |
| Compact Panel Mounting | 96 x 96 mm format suitable for standard electrical panel installation. |
| Power Logging | Designed with power logging for electrical consumption and operational analysis. |
| Power Quality Visibility | Displays voltage and current THD%, plus individual harmonics per phase up to the 31st harmonic. |
| Neutral Current Measurement | Helps detect phase imbalance and possible neutral conductor overload conditions. |
| 4-Quadrant Measurement | Supports consumption and generation monitoring across Q1, Q2, Q3 and Q4 quadrants. |
| Tariff Discrimination | Supports consumption discrimination across three tariffs using digital inputs. |
| Alarm and Control Outputs | Includes 2 relay outputs and 2 transistor outputs for alarm control or pulse output applications. |
| Industrial Communications | RS-485 communication with Modbus/RTU and BACnet protocol support. |
| Local Display Interface | Backlit LCD with user-defined parameter display, graphical active power display and LED alarm indication. |
| Application | Description |
| Energy Monitoring | Monitor consumption and generation in LV and MV electrical installations. |
| Tariff / Shift Analysis | Discriminate consumption into three tariffs, useful for work shifts or multiple energy sources. |
| Generator / PV / Grid Segregation | Use digital inputs to separate energy use from grid, generator or photovoltaic generation. |
| Power Quality Monitoring | Track THD% and individual harmonics up to the 31st harmonic for voltage and current. |
| Neutral Overload Detection | Measure neutral current to support imbalance and neutral conductor loading analysis. |
| Alarm and Automation | Generate alarm or pulse outputs based on measured or calculated electrical parameters. |
| Parameter | CVM-C11-ITF-IN-485-ICT2 |
| Product type | Power analyzer, panel mounted |
| Panel format | 96 x 96 mm |
| Model | CVM-C11-ITF-IN-485-ICT2 |
| Code | M58541 |
| Measuring channels | 4 |
| Input current | .../5 A or .../1 A |
| Communications | RS-485 |
| Protocols | Modbus/RTU and BACnet |
| Harmonics | Up to 31st harmonic |
| Digital inputs | 2 |
| Relay outputs | 2 |
| Transistor outputs | 2 |
| Power supply | 100...270 Vac/dc |
| Specification | Value |
| Installation category | CAT III 300 V |
| Consumption | 2 ... 5 VA |
| Frequency | 50 ... 60 Hz |
| Nominal voltage | 100 ... 270 V ~ ±10% |
| Specification | Value |
| Installation category | CAT III 300 V |
| Nominal voltage | 100 ... 270 Vdc ±10% |
| Specification | Value |
| Size (W x H x D) | 96 x 96 x 67.2 mm |
| Envelope | Self-extinguishing V0 plastic |
| Fastening | Panel |
| Weight | 0.353 kg |
| Protection class | IP54 front, IK08 |
| Relative humidity | 5 ... 95%, without condensation |
| Storage temperature | -25 ... +75 °C |
| Working temperature | -25 ... +70 °C |
| Specification | Value |
| Installation category | CAT III 300 V |
| Nominal current (In) | 5 A - .../5 A, .../1 A |
| Phase current measuring range | 1 ... 120% In (50 mA ... 6 A) |
| Minimum current measurement | 10 mA |
| Specification | Value |
| Installation category | CAT III 300 V |
| Input impedance | > 1.7 MΩ |
| Frequency measuring range | 45 ... 65 Hz |
| Voltage measuring range | 5 ... 120% Un (11.5 ... 276 V) |
| Nominal voltage | 230 V Ph-N, 380 V Ph-Ph |
| Minimum measurement voltage (Vstart) | 10 V ~ |
| Maximum value | 300 V F-N / 520 V F-F |
| Specification | Value |
| Fieldbus (BACnet) | MS/TP |
| Fieldbus (ModBus) | RS-485 / RTU |
| Protocol | ModBus RTU / BACnet |
| Speed | 9600 / 19200 / 38400 bps for ModBus RTU and BACnet |
| Specification | Value |
| LED | 2 LED |
| Keyboard | 3 keys |
| Display type | LCD Custom COG |
| Specification | Value |
| Input/output insulation | 2000 V |
| Quantity | 2 |
| Type | NPN |
| Specification | Value |
| Electrical life at maximum load | 60 x 10³ cycles |
| Mechanical life | 10 x 10 v cycles |
| Maximum switching capacity | 625 VA / 75 W (AC1) |
| Specification | Value |
| Pulse width | 30 ms to 400 ms, programmable |
| Quantity | 2 |
| Type | NPN |
| Maximum frequency | 16 impulses/s |
| Maximum current | 50 mA |
| Maximum voltage | 24 Vdc |
| Specification | Value |
| Phase current measurement | 0.2% |
| Phase voltage measurement | 0.2% |
| Active power measurement (kW) | 0.5% ± 2 digit |
| Reactive power measurement (kvar) | 1% ± 2 digit |
| Specification | Value |
| Maximum height | 2000 m |
| Installation category | CAT III 300 V |
| Contamination level/class | Pollution resistance 2 |
| Applicable standards | EN IEC 61326-1, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11, EN 61010-2-030, EN IEC 61557-12, EN 61010-1, UNE-EN 60068-2-2, UNE-EN 60068-2-1, UNE-EN 60068-2-78 |
| Code | Type | Ch. | Input current | Trans. out | Relays | Dig. in | Comm. | Protocol | Harm. | Power supply |
| M58531 | CVM-C11-ITF-IN-ETH-ICT2 | 4 | .../5 A .../1 A | 2 | 2 | 2 | Ethernet | Modbus/TCP BACnet | 31 | 100...270 Vac/dc |
| M58541 | CVM-C11-ITF-IN-485-ICT2 | 4 | .../5 A .../1 A | 2 | 2 | 2 | RS-485 | Modbus/RTU BACnet | 31 | 100...270 Vac/dc |
| M58561 | CVM-C11-FLEX-IN-485-ICT2 | 4 | 100 mV/kA | 2 | 2 | 2 | RS-485 | Modbus/RTU BACnet | 31 | 100...270 Vac/dc |
| M58581 | CVM-C11-MC-IN-485-ICT2 | 4 | .../250 mA | 2 | 2 | 2 | RS-485 | Modbus/RTU BACnet | 31 | 100...270 Vac/dc |