In 2026, Staircase Pressurization TAB Testing is a non-negotiable life-safety requirement. Under the latest BOMBA (Jabatan Bomba dan Penyelamat Malaysia) regulations and MS 1472, pressurized staircases must serve as a "Smoke-Free Sanctuary" during a fire. For high-rise assets in Kuala Lumpur and Selangor, a failed pressurization test doesn't just mean energy waste—it means your building will not receive its annual Fire Certificate (FC).
At EKG M&E Sdn Bhd, we apply 34 years of mechanical engineering expertise to perform rigorous Testing, Adjusting, and Balancing (TAB) on life-safety air systems, ensuring your egress routes remain clear and pressurized when it matters most.
The goal of a pressurization system is to maintain a higher air pressure in the staircase than in the adjacent floor areas. This prevents toxic smoke from infiltrating the exit path.
The 50 Pa Standard: We balance the system to maintain a pressure differential of 50 Pascals (Pa) when the staircase doors are closed. This is the "Gold Standard" for preventing smoke entry.
Force Thresholds: While the pressure must be high enough to block smoke, it must not be so high that a person cannot open the door. We verify that the Door Opening Force does not exceed 110 Newtons (N).
Velocity Seal: When doors are open, the system must provide a minimum air velocity (usually 1.0 m/s to 2.0 m/s) across the doorway to "push" smoke back.
We utilize laboratory-grade digital micromanometers and thermal anemometers to provide the "Technical Truth" required for BOMBA inspections:
We measure the pressure differential between the staircase and every occupied floor. We adjust the Variable Frequency Drives (VFDs) and bypass dampers to ensure a consistent 50 Pa (with a common tolerance of +/- 5 Pa) across all levels of the building.
We simulate the "Egress Scenario" by opening a specific number of doors (as per design intent, usually the exit door and two others). We measure the air velocity at the door frames to ensure the system can maintain its "Aerodynamic Shield" even when the seal is broken.
Over-pressurization is as dangerous as under-pressurization. We calibrate the Barometric Relief Dampers or motorized vents at the top of the stairwell to ensure excess pressure is bled off safely, preventing the doors from "locking" shut due to air force.
Our TAB reports provide the "Physical Proof" required for your Professional Engineer (PE) and BOMBA submissions:
| Requirement | BOMBA / MS 1472 Standard | EKG Certified Performance |
| Minimum Pressure | 50 Pa (Doors Closed) | Verified 50 Pa to 55 Pa |
| Max Door Force | 110 N (11 kg equivalent) | Measured & Verified |
| Air Velocity | 1.0 m/s minimum | Certified 1.2+ m/s |
| Response Time | Rapid (BMS Triggered) | Tested & Logged |
| Fire Alarm Sync | Mandatory Interlock | Full Sequence Verified |
Annual Fire Certificate (FC) Renewal: BOMBA increasingly requires certified TAB reports from independent mechanical specialists before they will conduct their physical inspection.
Eliminating "Whistling" and Droning: Improperly balanced systems create high-velocity air leaks around door seals, causing irritating noise in high-end Grade-A offices.
System Longevity: We ensure the fans do not "surge" or operate at unstable frequencies, protecting your fire-safety motors from premature failure.
34 Years of Engineering Depth: Based in Kuala Lumpur, we understand the "Stack Effect" in tropical high-rises, where temperature differences between the top and bottom of a tower can significantly impact pressure readings.
Turnkey Documentation: You receive a comprehensive, digital "Fire Safety TAB Report" containing pressure maps, velocity logs, and engineering sign-offs.
BIM Coordination: We can update your facility models with the final performance data, ensuring your digital twin reflects your building's life-safety reality.
Is your staircase pressurization system a certified safety barrier or a potential liability? Contact EKG M&E Sdn Bhd today for professional Staircase Pressurization TAB Testing and secure the safety and compliance of your building.
Tingnan ang karagdagang mga detalye tungkol sa EKG M & E SDN BHD
Malaysia