In the 2026 industrial landscape, ISO Class 5 (Class 100) represents the "Aseptic Frontier."
At EKG (Malaysia) SDN BHD, we engineer ISO Class 5 systems that exceed ISO 14644-1 requirements while maintaining the star-rated efficiency needed for statutory energy audits.
An ISO Class 5 AHU must maintain a particle concentration of
Unidirectional Airflow (Laminar): Air must move in parallel streams from ceiling to floor at a uniform velocity of 0.3 m/s to 0.5 m/s (60–100 fpm).
Air Change Rates (ACR): Typical ISO 5 environments require 240 to 480 Air Changes per Hour.
Ceiling Coverage: To achieve laminar flow, 35% to 70% (and often up to 80% for high-spec labs) of the ceiling must be covered with H14 HEPA or U15 ULPA filters.
To manage the high static pressure ($1,000\text{--}2,500\ Pa$) of dense filter banks, the AHU must be a precision-engineered machine.
| Feature | Specification | EKG Advantage |
| Drive System | IE5 Direct-Drive EC Fan Array | N+1 Redundancy; 30% more efficient than VFD-AC. |
| Casing Rating | L1 Airtight / TB2 Thermal Break | Zero bypass leakage; Anti-sweat for 100% humidity control. |
| Internal Lining | SUS 304 / 316 Stainless Steel | Non-porous; withstands VHP (Vaporized Hydrogen Peroxide). |
| Pressure Control | Active Cascade Tracking | Maintains constant room pressure ($\pm 15\ Pa$) as filters load. |
| SFP Target | $< 1.1\ kW/m^3/s$ | Fully compliant with EECA 2024 energy standards. |
Cleanliness at this level is achieved through a multi-stage "Sieve" and active neutralization.
Stage 1 (Pre-filter G4/F7): Captures large particles to extend the life of clinical filters.
Stage 2 (F9/E10): Removes fine dust and protects the cooling coil from bio-fouling.
Stage 3 (H14 HEPA / U15 ULPA): Final terminal stage achieving 99.999% efficiency at 0.3 or 0.12 microns.
UV-C Germicidal (UVGI): Integrated 254nm lamps sanitize the coil surfaces, ensuring zero microbial "seeding" of the cleanroom.
ISO 5 processes (like semiconductor lithography or aseptic filling) are hypersensitive to drift.
Temperature Tolerance: We engineer for $\pm 0.1^{\circ}C$ stability using fast-acting electronic reheat and chilled water modulation.
Humidity Precision: Target 45% – 55% RH with $\pm 2\%$ control using desiccant cooling or precision steam humidification, critical for preventing static electricity or material degradation.
Vibration Control: For nanotechnology applications, the fan array is mounted on inertia bases with spring isolators to ensure zero mechanical vibration reaches the work zone.
In Malaysia, ISO 5 facilities face mandatory 6-month re-certification cycles.
In-Situ Testing: Every EKG unit includes built-in DOP/PAO test ports for filter leak scanning without breaking the room’s integrity.
EnMS Integrated Reporting: All environmental data (Particulate, $\Delta P$, Temp, $kW$) is fed into your Energy Management System (EnMS) for the Energy Commission's statutory audits.
BOMBA Fire Safety: All internal insulation and gaskets are non-shredding and Class 0 / B1 fire-rated.
Technical Integrity: We provide the full Validation Package (IQ/OQ) and performance mapping required for NPRA/FDA or semiconductor industry audits.
3D BIM Coordination: We resolve complex "High-Bay" ceiling clashes before they reach the site, ensuring the laminar flow path is never obstructed by other services.
Are your ISO 5 air change rates driving your energy costs too high for the 2026 audit? Contact EKG (Malaysia) SDN BHD today. We specialize in engineering high-purity systems that are sterile, silent, and ultra-efficient.
Lebih maklumat tentang EKG M & E SDN BHD
Malaysia