CVM-A1600 Power Quality Analyzer

CVM-A1600 Power Quality Analyzer

分类: Circutor 当前有货
欲了解更多详情,请游览我们的官方网站 saturnpyro.com

详情

Circutor Class A Power Quality Analyzer

CVM-A1600 Power Quality Analyzer

The Circutor CVM-A1600 is a high-performance, panel-mounted Class A power quality analyzer for medium- and low-voltage installations. It measures, records and displays electrical parameters and power quality events according to IEC 61000-4-30 Edition 3 and IEC 62586-2 test methods.

The unit captures voltage and current quality events with waveform evidence, supports harmonics and interharmonics analysis up to the 63rd order, and provides an 8-inch touchscreen with local and remote access through its built-in web server.

Circutor CVM-A1600 Power Quality Analyzer
Model CVM-A1610-ITF, code M57110
Power Quality Class Class A, IEC 61000-4-30 Ed.3
Display 8-inch touchscreen with web server
Integration Ethernet, RS-485, Wi-Fi, Modbus, IEC 61850

Product Summary

CVM-A1600 is designed for supply quality monitoring, PQ event investigation, waveform capture, electrical parameter measurement and standards-based reporting. It is normally installed at the company supply boundary, main distribution boards, critical feeders or high-consumption loads where power quality visibility is important.

Item Brief Description
Product name Circutor CVM-A1600 Power Quality Analyzer
Model in datasheet CVM-A1610-ITF
Code M57110
Main positioning Class A power quality analyzer for supply quality monitoring, PQ event recording, waveform capture and standards-based reporting.
Primary standards IEC 61000-4-30 Ed.3, IEC 62586-2, IEC 61000-4-7, IEC 61000-4-15, IEC 61557-12, IEC 62053-22, IEC 62053-24 and EN 50160 reporting.
Typical applications Main incomer, utility supply boundary, critical distribution boards, industrial plants, commercial facilities, VFDs, UPS systems, EV chargers and power-electronic loads.
Integration message Integrates with EMS, SCADA and cloud platforms via REST API, Modbus TCP, IEC 61850, RS-485 Modbus RTU and Ethernet protocols.

Typical Monitoring Workflow

CVM-A1600 helps maintenance and energy teams move from assumption-based troubleshooting to recorded electrical evidence, event waveform capture and standardised power quality reporting.

1 Measure Supply and Load
2 Record PQ Events
3 Capture Waveforms
4 Generate Reports
5 Integrate with EMS / IoTWatt

Value Proposition

  • Class A measurement according to IEC 61000-4-30 Edition 3 for reliable, standardised power quality data.
  • Records power quality events in voltage and current, including waveforms for event investigation.
  • Automated EN 50160 reporting helps simplify compliance checks and supply quality reporting.
  • 8-inch touchscreen for easy navigation through live values, historical data and recorded events.
  • Built-in web server for remote viewing, configuration and access to instantaneous and historical parameters.
  • Designed for medium- and low-voltage installations, including supply boundary monitoring and critical loads.
  • Supports integration through REST API, Modbus TCP, IEC 61850, RS-485 and Ethernet connectivity.
  • Suitable for permanent PQ monitoring, event investigation, energy monitoring and multi-site visibility.

Key Features

Class A Power Quality Analyzer

Provides standardised and reliable measurement data according to IEC 61000-4-30 Ed.3 and IEC 62586-2 methods.

PQ Event Recording

Captures voltage and current disturbances such as dips, overvoltages, interruptions and transients.

Waveform Capture

Stores event waveforms to support root-cause investigation and discussions with utilities or internal maintenance teams.

Harmonics and Interharmonics

Analyses harmonics and interharmonics up to the 63rd order for identifying distortion caused by VFDs, UPS, chargers and power electronics.

Flicker and Unbalance Monitoring

Measures flicker, voltage/current unbalance and THD/TDD to evaluate network quality and equipment stress.

8-Inch Touchscreen

Simplifies local operation and helps users view live values, history and events without specialist software.

Built-In Web Server

Allows remote access to instantaneous values, historical data and device configuration.

EN 50160 Reporting

Automatically generates power quality reports against EN 50160 limits, including conclusions that can be emailed or sent to remote servers.

EMS and Cloud Integration

Supports APIRest, Modbus TCP, IEC 61850, RS-485 Modbus RTU, HTTPS, NTP, DNS, WSS, SFTP, FTP and SMTP.

Application Copy

The CVM-A1600 is typically installed at the company supply boundary point, main distribution boards or key electrical connection points, operating in parallel with the billing meter. It is also suitable for monitoring high-consumption or power-quality-sensitive loads such as motors, furnaces, PLC-controlled process lines, UPS systems, EV chargers, variable frequency drives and other power-electronic equipment.

Best-fit use case: Permanent Class A power quality monitoring at incoming supply, critical feeders, major loads and facilities where recorded electrical evidence is needed for troubleshooting, compliance or reliability improvement.

Main Technical Specifications

Parameter Specification
Product / modelCVM-A1610-ITF, Code M57110
CertificationIEC 61000-4-30
Power supply100...300 Vac/Vdc
AC supply frequency47...63 Hz
AC consumption14...20 VA
DC consumption8.5...9 W
Auxiliary battery autonomy20 s
Input current.../5 A .../1 A 250 mA
CommunicationsEthernet RS-485 Wi-Fi
Serial communicationRS-485, Modbus RTU
Network interface2 × Ethernet 10BaseT / 100BaseTx, RJ45
Network protocolsHTTPS, NTP, DNS, WSS, SFTP, FTP, IEC 61850, SMTP, Modbus TCP
Display8-inch touchscreen
MountingPanel mounting, DIN 43700 cut-out 138 × 138 mm
Size201 × 145 × 131 mm
Weight0.95 kg
ProtectionIP40 front, IP30 unmounted
Working temperature-20...+65 °C
Storage temperature-20...+80 °C
Relative humidity5...95%, without condensation

Measurement Circuits

Circuit / Parameter Specification
Voltage nominal range110...480 V Ph-N, 190...830 V Ph-Ph
Voltage measuring range10...600 V~ Ph-N
Frequency measuring range42.5...69 Hz
Input impedance2 MOhm
Minimum measurement voltage10 V Ph-N, 17 V Ph-Ph
Voltage circuit installation categoryCAT III 600 V (2000 m), CAT III 300 V (5000 m)
Current nominal input.../5 A for IEC 61000-4-30, .../1 A, .../0.250 A
Phase current measuring range0.01...6 A (.../5 A) IEC 61000-4-30; 0.01...12 A (.../1 A); 0.01...0.3 A (.../0.250 A)
Neutral current measuring range0.01...6 A (.../5 A); 0.01...12 A (.../1 A); 0.01...0.3 A (.../0.250 A)
Maximum pulse current15 A (.../5 A)
Minimum current measurement0.01 A
Maximum input current consumption0.9 VA
Current circuit installation categoryCAT III 600 V (2000 m), CAT III 300 V (5000 m)

Measurement Accuracy / Class

Measurement Accuracy / Class
Phase voltage±0.1% Un, class 0.1 (10%...150%), Class A IEC 61000-4-30
Neutral voltage±0.1% Un, class 0.1 (10%...150%)
Phase current0.2% (0.01...10 A) (.../5 A), Class A IEC 61000-4-30
Neutral current0.2% (0.01...10 A) (.../5 A)
FrequencyClass 0.02 (42.5...69 Hz), ±10 mHz IEC 61000-4-30
Active powerClass 0.2 ±1 digit IEC 61557-12
Reactive powerClass 0.5 ±1 digit IEC 61557-12
Active energyClass 0.2S IEC 62053-22
Reactive energyClass 0.5S IEC 62053-24
Power factorClass 0.5 IEC 61557-12
Voltage THDClass A IEC 61000-4-30 and Class I IEC 61000-4-7 (0.2%...100%)
Current THDClass A IEC 61000-4-30 and Class I IEC 61000-4-7 (0.2%...100%)
Voltage harmonics (THD)Class A IEC 61000-4-30 and Class I IEC 61000-4-7, ±0.15% (0.08%...200%)
Flicker Pinst / PstClass A IEC 61000-4-30 and Class F1 IEC 61000-4-15 (0...10 Pst)
Voltage unbalance KdClass A IEC 61000-4-30, ±0.15% (0%...200%)
Current unbalance KdClass A IEC 61000-4-30, ±0.15% (0%...200%)

CVM-A1600 Model Range

Code Type Power Supply Input Current Transistor Outputs Relays Digital Inputs Communications
M57110 CVM-A1610-ITF 100...300 Vac/Vdc .../5 A .../1 A 250 mA 0 0 0 Ethernet RS-485 Wi-Fi
M57111 CVM-A1611-ITF 100...300 Vac/Vdc .../5 A .../1 A 250 mA 6 2 6 Ethernet RS-485 Wi-Fi
M57112 CVM-A1612-ITF 100...300 Vac/Vdc .../5 A .../1 A 250 mA 12 4 12 Ethernet RS-485 Wi-Fi
Variant note: For this webpage, lead with M57110 / CVM-A1610-ITF as the main product. Include M57111 and M57112 as available variants for projects requiring additional I/O.

Customer Pain Points and Application Mapping

Customer Issue Relevant CVM-A1600 Capability Webpage Angle
Unexplained production stoppages or machine trips Records dips, swells, interruptions and transients with waveforms. Identify whether disturbances are supply-related or internally generated.
Need to prove supply quality to utility or management Class A IEC 61000-4-30 measurements and automatic EN 50160 reports. Use standardised evidence rather than assumptions.
Sensitive PLCs, automation and control systems Detects voltage variations, disturbances, flicker and harmonic distortion. Reduce nuisance faults and unexpected resets.
Harmonics from VFDs, UPS, chargers or power electronics Harmonics and interharmonics analysis up to the 63rd order. Locate distortion sources and prioritise mitigation.
Multi-site PQ monitoring Connectivity with EMS, Scout platform / Quality Analyst and remote protocols. Centralise PQ data, events and alarms across plants or buildings.
Limited in-house PQ expertise 8-inch touchscreen, web server and automatic reports. Make power quality information easier for maintenance teams to interpret.

Integration with IoTWatt 4.0

CVM-A1600 can be used as a high-quality power quality data source for IoTWatt 4.0 deployments where supply quality, event records, harmonics, unbalance and waveform evidence need to be reviewed together with energy consumption, demand, equipment operation and energy efficiency analytics.

  • Monitor incoming supply quality together with energy and demand data.
  • Review PQ events alongside production or equipment complaints.
  • Use PQ evidence to support troubleshooting, utility discussions and reliability improvement.
  • Integrate with EMS, SCADA, cloud dashboards and IoTWatt 4.0 analytics workflows.
  • Support permanent PQ monitoring for critical manufacturing, commercial and infrastructure sites.
  • Combine power quality monitoring with EECA, energy audit and digital energy performance reporting.

Product Visuals and Event Analysis

CVM-A1600 power quality monitoring screen and waveform capture
Power quality event and waveform monitoring visual
CVM-A1600 power quality dashboard and monitoring interface
Power quality monitoring interface and analysis view
ITIC curve event severity visual for power quality analysis
ITIC curve / event severity visual for disturbance evaluation

Recommended Deployment Checklist

  • Confirm whether the analyzer will be installed at incoming supply, MDB, critical feeder or selected load.
  • Confirm voltage level, wiring configuration and CT ratio before ordering and installation.
  • Select the correct model variant based on I/O requirements and integration needs.
  • Confirm communication method: Ethernet, RS-485, Wi-Fi, Modbus TCP, Modbus RTU, REST API or IEC 61850.
  • Define PQ event thresholds, report requirements and EN 50160 reporting workflow.
  • Confirm panel cut-out, power supply, network access and remote viewing requirements.
  • Plan data integration with EMS, SCADA, Circutor platform or IoTWatt 4.0.
  • Verify CT and voltage connections during commissioning before relying on PQ reports.
Engineering note: Final model selection, CT ratio, wiring configuration, communication setup and reporting requirements should be confirmed against the latest Circutor datasheet and project installation conditions.

CVM-A1600 Supply, Configuration and Power Quality Monitoring Support

Saturn Pyro supports Circutor CVM-A1600 Class A power quality analyzer supply, installation support, communication configuration, PQ monitoring, event review and integration with EMS, SCADA and IoTWatt 4.0 energy intelligence projects in Malaysia.

Enquire Now

更多 Saturn Pyro Sdn Bhd 相关资料
Saturn Pyro Sdn Bhd
Saturn Pyro Sdn Bhd Energy Meters Supplier Johor Bahru (JB), Energy Management Malaysia, Selangor, Power Quality Analyzers Supply Kuala Lumpur (KL), Penang ~ Saturn Pyro Sdn Bhd